Surface hand pump is not recommended. Normally the one way valve in these pumps cannot have reliability required for oil well to maintain pressure in the control line. So one day some smart operator will pressurised the line and close the valve in well head to isolate the pump. At that point naturally well will not be flowing. After opening the valve the flowing well fluid will raise the temp Of control line which will expand the control line fluid raising its pressure . And many a time this increase in pressure is sufficient to rupture seal of control valve or initiate leakage in the system.use of Fusible plug is not recommended in such situation. No authority will allow subsurface safety valve system with fusable plug.
Why to complicate the processes. You can assemble simple control panel on short notice for temporary use. We did it long time back . P.k.borthakur
Sent from my iPad
------Original Message------
Dear team,
One of our companies due to the long period delivery of a surface pump to be connected to SCSSSV, they used a hand pump to get the pressure required to keep the down hole valve opened and regularly check the pressure until have the surface pump in place (Two / Three months) foe an offshore well.
My question: is there any side effects from using the hand pump to open the valve and connect the control line with a Fusible plug for just in case a fire happened or damaged the oil will be leaked and the valve will be closed?
And in accordance to the effect of the temperature on the expansion / Contraction of the oil in the control line will be overcome by regular check to the line pressure.
If this manner is accepted, one could save a lot of cost by not buying the surface control panel equipped with a pump that work automatically !!!
Your feed back is highly appreciated.